Waste Water Treatment
Plant
Sampling
An
automatic sampler is used to sample from the influent channel just
upstream of the bar screen.
Final
Effluent is sampled after all treatment units just prior to discharge
to Rocky Fork of the Mohican River.
Both
influent and effluent are 24 hour period composite samples
proportionate in volume to the wastewater flow rate at the time of
sampling and representative of the facility’s overall performance.
Samplers have refrigeration units that maintain sample
temperature at 4 degrees C.
The
plant operator collects samples from the automatic samplers at
approximately 6:30 AM by replacing the filled containers (plastic)
with clean containers and transporting samples directly to the
laboratory. Samples are
allowed to stand at room temperature while calibration checks are
performed. Analysis
begins at 7:30 AM.
The
plant operator performs grab sampling during the mid morning.
Samples are collected in plastic bottles for direct transport
to the laboratory. Samples
for pH, dissolved oxygen and chlorine residual (summer only) are
tested immediately. Samples
for fecal coliform are collected in a sterilized glass bottle
containing a drop of 10% sodium thiosulfate solution.
Testing is initiated shortly thereafter.
Processed
sludge for the required Sludge Characteristic Report is collected
during a normal 8 hour run of the solids processing unit by the filter
building operator and transported directly to the laboratory where lab
technicians perform required tests.
Processed
sludge tests for heavy metals and other required parameters are
performed from 24-hour composite sample.
Receiving
streams – upstream of effluent discharge at South Illinois Avenue
Bridge and downstream of effluent discharge at State Route 39 Bridge
are collected as grab samples (one per month) and tests performed
shortly thereafter.
All
the wastewater and processed sludge samples which are transported to a
commercial laboratory for special tests (Cyanide, Volatile Organics,
etc.) are handled using sample preservation procedures, container
materials and maximum allowable holding times required by state and
federal laws.
Sample
bottles are permanently labeled for their appropriate use.
Chain
of custody bench sheets are used between Wastewater Treatment Plant
and commercial laboratory.